Modular network-generator installation switches implement the 1-0-2 switching program, which makes it possible, for example, to connect one of two input lines to the output or completely disconnect the circuits. The switch contacts function as a disconnector, so it is possible to switch to the rated load current
Rotary modular network switch – PSR-480
Rotary modular network switch – PSR-480 unit
SKU: PSR-480
Category: Network-aggregate switches
- Function
- disconnector, direction switch
- Drive
- manual, rotary
- Rated switching voltage Ue (AC)
- 415 V
- Rated current [AC-21B/AC-22A]
- 80 A
- Insulation voltage Ui
- 800 V
- Surge voltage Uimp
- 8 kV
- Number of poles
- 4P
- Switching program
- 1-0-2
- Mechanical strength
- 10000 cycles
- Rated frequency
- 50÷60 Hz
- Current load capacity AC21 (category A and B)
- 80 A
- Current load capacity AC22 (category B)
- 80 A
- Current load capacity AC23 (category B)
- 80 A
- Switching power
- 52 kW
- Power loss (for rated current) per pole
- 2.4 W
- Power loss (for rated current) total
- 9.6 W
- Connection
- screw terminals
- Cable diameter (minimum)
- 2.5 mm²
- Wire diameter (maximum)
- 35 mm²
- Operating temperature
- -20÷50°C
- Dimensions
- 8 modules (width: 135 mm, height: 94 mm, depth: 104 mm)
- Mounting
- DIN rail or mounting plate
- Protection class
- IP20
Switching Diagram
Sample Application